Line clearance
Line deflection diagram
Legend
- Conductor A, tower 1X: -4.40 m, Y: 0.00 m, Z: 28.81 m
- Conductor A, tower 2X: -4.40 m, Y: 310.00 m, Z: 28.81 m
- Conductor B, tower 1X: 0.00 m, Y: 0.00 m, Z: 25.00 m
- Conductor B, tower 2X: 0.00 m, Y: 310.00 m, Z: 25.00 m
Governing minimum clearance — load cases at the sampled curve positions (shortest 3D distance). Cross-wind direction: −1 (right → left, −X)
| Conductor | Load case | Ice load [N/m] | Wind load [N/m] | Sag [m] | X at span [m] | Z at span [m] | Tension [MPa] | Conductor blow-out [°] | Angle chain 1 [°] | Angle chain 2 [°] |
|---|---|---|---|---|---|---|---|---|---|---|
| Conductor A (2) | CD (C→D, t≈1.00) | 19.390 | 10.266 | 9.982 | -7.381 | 20.002 | 171.72 | -18.70 | 0.00 | 0.00 |
| Conductor B (1) | AB (A→B, t≈0.00) | 0.000 | 9.800 | 7.762 | -4.521 | 14.249 | 47.68 | -21.62 | -25.62 | -24.02 |